Ampac

Fire Fan Module

Product Overview

The Fire Fan Module controls and monitors Dampers, Fire Fans and Sprinkler Pumps.

Four (4) individual sets of controls are provided per module with each incorporating a separate Start and Stop control switch and associated output relay. A single control/indication for plant trip reset is also provided.

Individual control LED Status indication and associated inputs are provided for On, Off and Auto. Up to three (3) Status inputs can be monitored per Fan or Damper for Run, Fault and Stop which are programmed via the FireFinder control panel.

Individual label inserts and title descriptor can be modified on site to suite appropriate application.

A hard-wired version of a fire fan module consists of a Fire Fan Control Card and Termination Board. Field wiring is terminated to the termination board at the FACP.

A loop-driven version is also available and in this configuration only the Fire Fan Control Card would be required. Field wiring will terminate to address input/output devices that operate on the addressable loop.

Features

  • Four (4) Controls per Module
  • Status indication for Run / Fault / Stop
  • Controls for ON / Auto / Off
  • Audible and visual feedback of button press
  • Built in Plant Trip Reset
  • Supports 3, 4 and 5 Wire Connections
  • Available in Hardware or loop driven versions
  • AS1668 Approved

Specifications

Voltage

24 Vdc

Quiescent current

Hardwired

Loop Driven

 

35 mA

10mA

Control Outputs

200 mA @ 27 Vdc

Relay contact rating

3 Amp at 24 Vdc

Operating temperature

-5°C to 55°C (no icing)

Relative Humidity

0 to 95% (non condensing)

Weight

230 grams

System Capacity

15 max per panel

Item Numbers

4310-0021

Fire Fan Module (hardwired version)

4310-0071

Fire Fan Module (loop version)

LAB1486

Label Template