Ampac

Heat & Mounting Base

Product Overview

There are two heat detectors in the Xpander range designed to suit a wide variety of operating conditions. A static heat detector (CS) which responds only when a fixed temperature has been reached and a rate-of-rise detector (A1R) which has a fixed upper limit, but in addition, measures the rate of increase in temperature.

Features

  • Can be used in applications where smoke detectors are unsuitable.
  • Ideal environments that are dirty or smokey under normal conditions.
  • CS detectors are ideal for use in environments with rapid temperature fluctuations such as boiler rooms.
  • Bi-directional (monitored) radio platform.
  • Easy to install.
  • Powered by two independent battery packs.
  • Five year battery life using standard of AA alkaline batteries.

 

Approvals: AS7240-5 and AS4428-9

Specifications

Voltage (regulated from radio base) 3VDC
Size inc base 105mm D x 80mm H
Operating temperature -10°C to +50°C (no icing)
Relative humidity 0 to 95% (non condensing)
IP rating IP23D
Weight inc base 400 grams

Item Numbers

Rate-of-Rise (A1R) 4106-5301
Static (CS) 4106-5302