Intelligent Input/Output Unit

Product Overview

The Soteria Input Output Unit provides supervision of one or more normally open contacts connected to a single pair of cables and a set of changeover relay output contacts.

Features

Improved design for ease of wiring meaning faster installation

• Short circuit isolator

Address range 1 – 126

• Compatibility with XP95 and Discovery protocol

Failsafe mode (meets BS 7273-4 requirements)

 

Specifications

Supply Voltage (Vmin—Vmax)

17 to 35V dc

Protocol

5-13V peak to peak

Power-up surge current

900uA

Quiescent current

500uA

Max Current LEDs On

3.5mA

Max current LEDs disabled

500uA

Relay output contact rating

1A at 30V dc or ac

Isolator data

Refer to short-circuit isolation  datasheet PP2090  

Operating Temperature

-40°C + 70°C

Humidity

0% to 95% RH (no               condensation or icing)   

Vibration, impact and shock

EN54-17 & EN54-18

Standards & Approvals

EN54-17, EN54-18, CPR and LPCB

Dimensions

60mm height x 150mm width x 90mm depth

Weight

244g

Item Numbers

SA4700-102AMP 

Ampac Input Output Device