Ampac

Titanus Micro-Sens

Product Overview

TITANUS MICRO•SENS® air sampling smoke detection system was developed as a cost-effective solution for monitoring small to medium-sized spaces and equipment.

 With the optional ROOM IDENT, this device makes use of patented technology that enables it to monitor up to 5 rooms or facilities and to identify the source of the alarm.

 TITANUS MICRO•SENS® is available in a cold storage option, with a redundant fan, or as a detector box. The detector box option does not have its own fan and can be used in combination with TITANUS® systems to localise the sampling hole where the smoke is entering.

TITANUS MICRO•SENS® air sampling smoke detection system can be used to replace up to 8 point-type smoke detectors. This requires up to 50m of pipe, regardless of whether Class A, B or C is required in accordance with AS7240.20

Features

  • Compact and cost-effective air sampling smoke detection system
  • Robust & Efficient High Powered Light Source (HPLS) Detection Technology
  • LOGIC·SENS Fire Pattern Recognition Technology
  • Freezer Version Operates in -40Deg to +60DegC with No Heater Boxes Required
  • Optional individual room detection of the source of the fire with ROOM IDENT
  • 1 to 2 alarm thresholds
  • Optional smoke level display in bar graph form
  • A BlowFree System for programmed or Automated On-Demand Pipe Cleaning
  • Optional with redundant fan
  • Available without a fan as a detector box
  • A Powerful & Efficient Aspirator Allowing up to 50m of Pipework with up to 8 aspiration apertures
  • Time Saving Installation & Commissioning Via Plug & Play Setup
  • Large Capacity 3-Stage Filters with Selectable 1-15 Micron Ratings
  • A Large Range of Fittings, Pipework and Sampling Points
  • Noise silencer available

Specifications

Detector Unit MICRO·SENS®
Number of Sensor Modules Fitted 1
Max. Number of Sampling Holes 8
Max. Total Pipe Length Capable 50m
Weight 850 to 895g – depends on configuration
Current – Start Up Maximum: 150mA
Current – Quiescent (at 24 VDC) 105mA
Current – Alarm (at 24 VDC) 110-140mA (9V ventilator voltage)
Operating Voltage 24 VDC (14 – 30 VDC)
Tapered Pipe Connectors 2 x 25mm
Detector Dimensions (W x H x D) 144 x 222 x 70 mm
Housing Colour RAL 9018, Papyrus White
Cabinet Type, Rating ABS Plastic, IP20 (IP54 with air return)
Temperature – Standard Version -20 °C to + 60 °C
Temperature – Freezer Version -40 °C to + 60 °C
Humidity (Permanent) 10-95% Rel. Non-Condensing
Cable Entries 8 x M20, 2 x M25
Sensor Head Sensitivities 0.5% and 0.1%
Interface Types Relays
Alarms 2 Adjustable Alarm Threshold
Fault Signals
  • Air Flow Low
  • Air Flow High
  • Processor/Hardware Fail
  • Ventilator Fail/Air Stabilising
Clamped Connections Max. 1.0 mm²
Front Panel Control & Indications

Operational: Green Fire alarm: Red Action alarm: Red (optional)

Fault: Yellow Smoke Level: 10 x Yellow bar graph (optional) Alarm location: 5 x Red (optional)

Noise Level

Standard & Freezer – 40 dB(A).

Reduction by 10dB(A) possible by using the noise suppressor (AD-10-0005)

Event Log Inbuilt, access thru Diag Tool
Redundant Fan Optional

 

Item Numbers

7010-6001/6002 MicroSens 0.5% / 0.1%
7010-6011/6012 MicroSens 0.5% / 0.1% Bar Graph
7010-6100/6101 MicroSens 0.5% / 0.1% Freezer
7010-6110/6111 MicroSens 0.5% / 0.1% Freezer and Bar Graph
7010-6301/6302 MicroSens 0.5% / 0.1% Room Ident
7010-6311/6312 MicroSens 0.5% / 0.1% Bar Graph and Room Ident