Product Overview

The XP95 Heat Detector monitors temperature by using a single thermistor network which provides a count output proportional to the external air temperature. The XP95 range features two Heat Detectors, standard and high temperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C. The high temperature detector, classified as a CS device, will report an alarm at 90°C.

Features

  • Ideal in environments that are dirty or smokey under normal conditions.
  • Well suited for warehouses, loading bays and car parks.
  • Unaffected by wind or atmospheric pressure.

Specifications

Voltage

17-28 VDC

Quiescent current

250?A at 24 VDC

Alarm current

2mA at 24 VDC

Size inc base

100mm Dia x 50mm H

Operating temperature

A2S:-20°C to +70°C (no icing)

Relative humidity

0 to 95% (non condensing)

IP rating

IP23D (indoor use)

Weight inc base

157 grams

Item Numbers

55000-420AMP

XP95 Heat Detector Standard A2S (55°C) – EMC

55000-401AMP

XP95 Heat Detector High Temp – CS (90°C) – EMC