Ampac

XP95 Integrated Base Sounder

Product Overview

The Integrated Base Sounder comprises a sounder with integral detector mounting base and has been designed to signal a fire alarm in enclosed areas. The sounder is line powered requiring no external power supply and is designed for internal use.

Alert and Evacuation sounder tones complying with the recommendations of AS7240-3 are incorporated which are fully programmable for staged evacuation within the LoopSense and FireFinder control panels.

The low volume range is useful in areas such as hospitals where a fire alert is initially intended to warn staff only. The sounder is set to high volume range for general use.

Synchronisation of tones ensures the integrity of the alarm signal/tones from different sounders do not merge into one signal that could be  mistaken for a different tone.

For systems requiring isolators at every point the built-in isolator saves installation time and cost.

The built in acoustic self-test enables the sounder to  listen to itself when it is switched on and if no sound is detected, a fault signal will be transmitted when the sounder is polled to the control panel. The sounder base can be used either with a detector fitted or with a cap for operation as a stand-alone alarm device.

Features

  • Two volume ranges
  • Alert and Evacuate tones
  • Synchronisation of tones
  • Individual and group addressing
  • Built-in short circuit isolator
  • Unique acoustic self-test
  • Complies with AS7240-3

Specifications

Operating Voltage

17 to 28 VDC

Quiescent current

 200µA

Sounder operated

5mA

Sound output

Max 86db Min 69dB

Sound pattern

520Hz +/- 5% on a temporal 3 pattern (ISO8201)

Dimensions

115mm x 38mm

Weight

140 grams

Operating temperature

-20°C to +60°C

Humidity (no condensation)

0 to 95%

IP rating

21D

Sounder type

Type A

Approval

AS7240-3:2014

Item Numbers

4107-4001

XP95 Integrated Base Sounder

201-0114

XP95 White Base Sounder Cap

201-0119

XP95 Red Base Sounder Cap