Soteria Input Output Unit

Soteria Input Output Unit

The Soteria Input Output Unit provides supervision of one or more normally open contacts connected to a single pair of cables and a set of changeover relay output contacts.

The Soteria Input Output Unit is available in the new faceplate style enclosure. This can be surface mounted with the supplied back-box or flush mounted using a UK double gang, flush mounting back-box of a minimum 30mm depth.

  • Improved design for ease of wiring meaning faster installation
  • Short circuit isolator
  • Address range 1 - 126
  • Compatibility with XP95 and Discovery protocol
  • Failsafe mode (meets BS 7273-4 requirements)

Approvals: AS ISO 7240.18:2015







    Supply Voltage (Vmin—Vmax) 17 to 35V dc
    Protocol 5-13V peak to peak
    Power-Up Surge Current 900µA
    Quiescent Current 500µA
    Max Current LEDs On 3.5mA
    Max Current LEDs Disabled 500µA
    Relay Output Contact Rating 1A at 30V dc or ac
    Isolator Data Refer to short-circuit isolation datasheet PDS201-9001
    Operating Temperature -40°C + 70°C
    Humidity 0% to 95% RH (no condensation or icing)
    Vibration, Impact, and Shock EN54-17 & EN54-18, AS7240.17 & AS7240.18
    Standards & Approvals EN54-17, EN54-18, CPR, LPCB, AS7240.17, AS7240.18 & SAI Global
    Dimensions 60mm H x 150mm W x 90mm D
    Weight 244 grams