Soteria Twin Input Output Unit
The Soteria Twin Input Output Unit provides the function of two Input Output Units within one enclosure. The two units are electrically independent of each other. There is a DIL switch on each unit to set the address.
Both Input Output units in the enclosure provide supervision of one or more normally open volt free contacts connected to a single pair of cables and a set of changeover relay output contacts.
- Remote Indication of Concealed Fire Detection
- High Contrast LED Indicator
- Wide Area Illumination
- Audible Indication of Concealed Detection
- Compatible with Addressable and Conventional Systems
- Range of Text Legends
- Integral Buzzer with Mute option
Approvals: AS ISO 7240.18:2015
Supply Voltage (Vmin—Vmax) | 17 to 35V dc |
Protocol | 5-13V peak to peak |
Power-Up Surge Current | 900µA per Input Output Unit |
Quiescent Current | 500µA per Input Output Unit |
Max Current LEDs On | 3.5mA per Input Output Unit |
Max Current LEDs Disabled | 500µA per Input Output Uni |
Relay Output Contact Rating | 1A at 30V dc or ac |
Isolator Data | Refer to short-circuit isolation datasheet PDS201-9001 |
Operating Temperature | -40°C + 70°C |
Humidity | 0% to 95% RH (no condensation or icing) |
Vibration, Impact, and Shock | EN54-17, EN54-18, AS7240.17 & AS7240.18 |
Standards & Approvals | EN54-17, EN54-18, CPR, LPCB, AS7240.17, AS7240.18 & SAI Global |
Dimensions | 60mm H x 150mm W x 90mm D |
Weight | 281 grams |
4110-1103 | Soteria Twin Input Output Unit |