Vector Sounder



The Vector sounder has been designed for general purpose conventional fire detection applications and incorporates AS1670.4 compliant signal tones. The Vector sounder can be installed as a sounder base for Ampac conventional detectors or a surface mount sounder when used in conjunction with the optional lid.
- Alarm Signals to AS1670.4
- Externally powered
- Low current consumption.
- Volume control adjustment.
- Built-in synchronising circuitry with sounders on the same circuit.
- Low profile.
Operating Voltage | 8 to 35 VDC |
Supply Current Evac | 15mA @ 24VDC |
Supply Current Alert | 8 mA @ 24VDC |
Signal Output | AS 1670.4 |
Max. Output Level | 91 dBA @ 1 metre with detector |
Evac | 93 dBA @ 1 metre with lid |
Volume Control | - 30 dBA |
IP Rating | IP42 |
Temperature Range | -20 to + 70°C |
Construction | ABS |
Dimensions | 106mm Ø x 35mm H (Sounder & lid only) |
205-0077 | Vector Sounder |
205-0017 | Vector Sounder Lid |