UV Base Mounted Conventional Flame Detector
The Series 65 Base Mounted Ultraviolet (UV) Flame Detector is designed to protect internal areas where flaming fires may be expected.
The detector is sensitive to ultraviolet radiation emitted by flames during combustion. Since it requires only UV radiation, the Flame Detector also responds to stationary flames with no flicker such as cigarette lighters and blue gas flames. The detector is set to respond to ultraviolet radiation (185 to 260nm) emitted by almost all flames, including those invisible to the naked eye, e.g. hydrogen fires.
The detector has a single UV sensor with a narrow spectra response in order to discriminate between flames and most spurious sources of radiation and is designed for internal fully enclosed areas.
Caution: The detector will also detect electrical discharges from lightning or arc welding.
Note: When using the detector the following must be avoided; outside viewing, UV lamps, electrical sparkling, welding and sources of radiation, UV light sources, prolonged ambient temperatures above 60ºC, and obstructions to the field of view.
Supply Voltage | 12-33V DC |
Quiescent Current | 550uA |
Alarm Current | 61mA at 28V |
Range of View | 0.1m² n-heptane at 25m |
Sensitivity | Class 1 (EN54-10) |
Field of View | 90º cone |
Spectral Response | UV 185 to 260nm |
Operating Temperature | -40°C to +70°C (no condensation or icing) |
Storage Temperature | -40ºC to + 85ºC |
Relative Humidity | 0-95% (non-condensing) |
IP Rating | IP66 |
Dimensions | Detector: 100mm Ø x 40mm / Detector & Base 100mm Ø x 48mm |
Weight | Detector: 150 grams / Detector & Base: 210 grams |
4108-1001 | Series 65 UV Flame Detector |