ampac-logo-new-01 SoftwareTraining

Ampac Single Input Device

Ampac Single Input Device Ampac Single Input Device

The Ampac Single Input Device is designed to monitor the state of one or more single-pole, voltage-free contacts connected to a single pair of cables and to report the status to the Ampac Fire Alarm Control Panel. Monitoring of the external cables is provided for open and short circuit fault conditions and the input circuit itself is conditioned with de-bounce circuitry for enhanced noise rejection. The input circuit is also protected against high transient voltages.

The Ampac Single Input Device is loop-powered and incorporates bi-directional isolation circuitry to provide protection against detection loop short circuits. Onboard LED status indication is provided for service and commissioning purposes, a feature that can be deactivated during normal operation to reduce the current draw on the system.

Two packaging options are available. The ‘DIN Mount’ version enables the device to be mounted onto a standard 35mm DIN rail or screwed direct to the back pan of a larger enclosure, while the ‘Enclosed’ version allows the device to be surface mounted to a wall.

  • Loop Powered
  • Monitored Input
  • Compatible with XP95 & Discovery Protocol
  • Built In Short Circuit Isolator
  • Low Power Consumption
  • Diagnostic LED Indications
  • Surface Mount Enclosure
  • DIN Rail Mount Option







    Operating Voltage 17 - 28 VDC
    Max Current at 24V DC LEDs Enabled LEDs Disabled
    Quiescent Current 1.84 mA 1.29 mA
    Input On 2.68 mA 1.51 mA
    Output Contact Rating  1A @ 30V AC or DC
    Operating Temperature  -20°C +70°C
    Humidity  0 to 95% Non-condensing
    Dimensions - DIN Mount H 75mm x W 110mm x 25mm
    Dimensions - Enclosed H 150mm x W 200mm x D 52mm
    Material Grey ABS
    IP Rating IP44 (Indoor Use)
    4210-0052 Single Input Device DIN Mount
    4210-0053 Single Input Device Enclosed