Ampac Single Input Device
The Ampac Single Input Device is designed to monitor the state of one or more single-pole, voltage-free contacts connected to a single pair of cables and to report the status to the Ampac Fire Alarm Control Panel. Monitoring of the external cables is provided for open and short circuit fault conditions and the input circuit itself is conditioned with de-bounce circuitry for enhanced noise rejection. The input circuit is also protected against high transient voltages.
The Ampac Single Input Device is loop-powered and incorporates bi-directional isolation circuitry to provide protection against detection loop short circuits. Onboard LED status indication is provided for service and commissioning purposes, a feature that can be deactivated during normal operation to reduce the current draw on the system.
Two packaging options are available. The ‘DIN Mount’ version enables the device to be mounted onto a standard 35mm DIN rail or screwed direct to the back pan of a larger enclosure, while the ‘Enclosed’ version allows the device to be surface mounted to a wall.
- Loop Powered
- Monitored Input
- Compatible with XP95 & Discovery Protocol
- Built In Short Circuit Isolator
- Low Power Consumption
- Diagnostic LED Indications
- Surface Mount Enclosure
- DIN Rail Mount Option
Operating Voltage | 17 - 28 VDC | |
Max Current at 24V DC | LEDs Enabled | LEDs Disabled |
Quiescent Current | 1.84 mA | 1.29 mA |
Input On | 2.68 mA | 1.51 mA |
Output Contact Rating | 1A @ 30V AC or DC | |
Operating Temperature | -20°C +70°C | |
Humidity | 0 to 95% Non-condensing | |
Dimensions - DIN Mount | H 75mm x W 110mm x 25mm | |
Dimensions - Enclosed | H 150mm x W 200mm x D 52mm | |
Material | Grey ABS | |
IP Rating | IP44 (Indoor Use) |
4210-0052 | Single Input Device DIN Mount |
4210-0053 | Single Input Device Enclosed |