Aspiris Cobalt
The Aspiris Cobalt HM Series is designed specifically for early smoke detection in small to medium-sized areas. The Cobalt Aspirating Smoke Detectors work by drawing air samples through a network of pipes to detect fire conditions at the earliest stages.
Equipped with a HSSD (High Sensitive Smoke Detection) chamber, this versatile device is available in both single-channel (Aspiris Cobalt HM1) and dual-channel models (Aspiris Cobalt HM2). Each channel features a pipe inlet, a front display, a HSSD chamber, an aspirator and flow sensor. They integrate a range of sensors such as smoke, temperature and humidity sensors offering advanced detection capabilities for various applications.
| Smoke detection light source |
High-power blue LED |
| Number of high sensitive smoke chambers |
HM1: 1 HM2: 2 |
| Smoke detection principle |
Forward light scattering mass detection |
| Smoke detection range | 0.02~25%/m |
| Alarm sensitivity range | 0.1~ 20%/m mm |
| Max. capillary tube/pipe length | 30 m |
| Pipe length (linear/branch) |
HM1: 105/260 m HM2: 2 x 105 m, 2 x 260 m |
| Max. no. of sampling holes (Class A/B/C) | HM1: 8 /16/32 HM2: 16 / 32 /64 |
| Voltage | 18 ~ 30Vdc |
| Current @24V | HM1: 145 mA~185 mA HM2: 290 mA~370 mA |
| Ambient temperature | 0 ~ 40°C |
| Sampling air temperature | -20 ~ 60°C |
| Humidity | 10~95% RH non-condensing |
| Dimensions | 321.7(h) x 154(l) x 97.4(w) mm) |
| Weight | HM1: 2.2 kg HM2: 2.3 kg |
| IP rating | IP51 |
More specifications are available in the Product Data Sheet and manual.
| Aspiris Cobalt HM1 | 7100-3001 |
| Aspiris Cobalt HM2 | 7100-3002 |
| Aspiris Cobalt HM1 exhaust adapter | 7100-3011 |
| Aspiris Cobalt HM2 exhaust adapter | 7100-3012 |
| Aspiris Cobalt HM I/O Board | 7100-3013 |
| Aspiris Remote Display Unit (RDU) | 7100-4000 |