XP95 Addressable Manual Call Point
The XP95 Manual Call Point has been designed to operate on a loop of intelligent addressable fire detection devices. The address of each call point is set at the commissioning stage by means of a seven-segment DIL switch. The device features plug-and-play terminal connections and a re-settable element.
- Plug-and-play terminal connectors for fast wiring
- Allows wiring continuity testing before fitting
- Isolated version available
- Reports an alarm in under 0.2 seconds
- Re-settable element
| Voltage | 17-28 V DC |
| Quiescent Current | 100µA at 24V DC |
| Alarm Current | 4mA at 24 V DC |
| Address Method | 7 segment DIL switch |
| Operating Temperature | -20°C to +60°C (no icing) |
| Relative Humidity | 0 to 95% (Non-Condensing) |
| IP Rating | IP24D (indoor use) |
| Size (surface mount) | 93mm H x 89mm W x 59.5mm D |
| Weight | 160 grams |
| 213-0050 | XP95 Manual Call Point (Surface) |
| 213-0051 | XP95 Manual Call Point with Isolator (Surface) |
| 213-0064 | XP95 Manual Call Point Protective Cover |