ampac-logo-new-01 SoftwareTraining

8 Zone Conventional Board

The 8 Zone Conventional Board provides 8 monitored conventional zones and connects to the Fire Alarm Control Panel via the internal dedicated RS485 communications port.

Each zone can accommodate up to 40 conventional detectors and can be programmed to function in one of the following modes: Normal (latching), Non-Latching/Self Reset, Dependency A, B, and C (EN54-2 and AS7240-2), and Alarm Investigation facility.

  • Supports up to 8 conventional zones.
  • Supports a range of conventional detectors.
  • Up to 40 detectors per zone.
  • Supports a range of resistive and capacitive End of Lines.







    Voltage 27 V dc
    Quiescent Current 25 mA (10uF EOL fitted)
    Alarm Current 25 mA (per zone)
    Operating Temperature -5°C to +55°C (no icing)
    Relative Humidity 0% to 95% (no condensation)
    Dimensions 72.5mm x 155mm
    Weight 120 grams
    System Capacity 15 Max
    4310-0082 8 Zone Conventional Board