Soteria Twin Input Output Unit
![Soteria Twin Input Output Unit](https://ampac.net/wp-content/uploads/2017/12/SA4700-104AMP-Soteria-Twin-Input-Output-Unit.png)
The Soteria Twin Input Output Unit provides the function of two Input Output Units within one enclosure. The two units are electrically independent of each other. There is a DIL switch on each unit to set the address.
Both Input Output units in the enclosure provide supervision of one or more normally open volt free contacts connected to a single pair of cables and a set of changeover relay output contacts.
- Remote Indication of Concealed Fire Detection
- High Contrast LED Indicator
- Wide Area Illumination
- Audible Indication of Concealed Detection
- Compatible with Addressable and Conventional Systems
- Range of Text Legends
- Integral Buzzer with Mute option
Approvals: AS ISO 7240.18:2015
Supply Voltage (Vmin—Vmax) | 17 to 35V dc |
Protocol | 5-13V peak to peak |
Power-Up Surge Current | 900µA per Input Output Unit |
Quiescent Current | 500µA per Input Output Unit |
Max Current LEDs On | 3.5mA per Input Output Unit |
Max Current LEDs Disabled | 500µA per Input Output Uni |
Relay Output Contact Rating | 1A at 30V dc or ac |
Isolator Data | Refer to short-circuit isolation datasheet PDS201-9001 |
Operating Temperature | -40°C + 70°C |
Humidity | 0% to 95% RH (no condensation or icing) |
Vibration, Impact, and Shock | EN54-17, EN54-18, AS7240.17 & AS7240.18 |
Standards & Approvals | EN54-17, EN54-18, CPR, LPCB, AS7240.17, AS7240.18 & SAI Global |
Dimensions | 60mm H x 150mm W x 90mm D |
Weight | 281 grams |
4110-1103 | Soteria Twin Input Output Unit |