Marine DIN-Rail Zone Monitor

The Marine DIN-Rail Zone Monitor powers and controls the operation of a zone up to 20 conventional fire detectors from a loop of XP95 addressable detectors and ancillary devices. This unit needs to be installed in a suitable enclosure.

The Marine DIN-Rail Zone Monitor features a built-in isolator, visible short-circuit LED, and is loop-powered.

Certification: ESC, ABS, VNIIPO & ESC







    Voltage 17 - 28 V dc
    Quiescent Current 4 mA + Detector Load
    Alarm Current 11 mA
    Operating Temperature -20°C to +70°C
    Relative Humidity 0% to 95% RH (no condensation or icing)
    IP Rating Designed to IP20
    Dimensions 110mm W  x 107mm H x 20mm D
    Weight 95 grams

    Please Note: All data is supplied subject to change without notice. Specifications are typical ay 24 V, 23°C and 50% RH unless otherwise stated.