Ampac

8 Zone Conventional Board

Product Overview

The 8 Zone Conventional board has been designed to interface with AMPAC’s range of Fire Alarm Control Panels (FACP).

The board supports 8 conventional zones and connects to the FACP via the internal dedicated RS485 communications port.

Each zone can accommodate up to 40 conventional detectors and can be programmed to function in one of the following modes:

  • Normal (latching)
  • Non-latching/Self Reset
  • Dependency A, B and C (EN54-2 and AS7240-2)
  • Alarm Investigation facility

 

Supports either a 3K3Ω, 4K7Ω, 6K8Ω or 10KΩ resistor values or a 10uF capacitor as the end of line on all zones.

LPCB Approved.

 

Specifications

Voltage 27 V dc
Quiescent Current 25 mA (10uF EOL fitted)
Alarm Current 25 mA (per zone)
Operating Temperature -5°C to +55°C (no icing)
Relative Humidity 0% to 95% (no condensation)
Dimensions 72.5mm x 155mm
Weight 120 grams
System Capacity 15 Max

 

Item Numbers

4310-0082 8 Zone Conventional Board